5.6 Analog inputs
Objects with measured values and status information from the pump
ID Object name R/W Description Unit LC 2X1 LC 2X2
AI, 0 Fault code R Grundfos fault code. - ● ●
AI, 1 Warning code R Grundfos warning code. - ● ●
AI, 2 HighLevel R High level in centimetres. cm ● ●
AI, 3 StartLevelPump1 R Start level for pump 1 in centimetres. cm ● ●
AI, 4 StopLevelPump1 R Stop level for pump 1 in centimetres. cm ● ●
AI, 5 StartLevelPump2 R Start level for pump 2 in centimetres. cm ● ●
AI, 6 Pit water level R Pit water level in centimetres. cm ● ●
AI, 7 Pit power consumption R Pit power consumption in watts. W ● ●
AI, 8 Pit energy consumption R Pit energy consumption in kilowatt hours. kWh ● ●
AI, 9 Pit running time R Pit running time in minutes. min ● ●
AI, 10 Analog Input 1 (AI1) R Analog Input 1 % ● ●
AI, 11 Analog Input 2 (AI2) R Analog Input 2 % ● ●
AI, 12 Analog Input 3 (AI3) R Analog Input 3 % ● ●
AI, 13 Pump1 time to service R Pump 1 time to service in minutes. min ● ●
AI, 14 Pump2 time to service R Pump 2 time to service in minutes. min ● ●
AI, 15 Pump1 start counter R Pump 1 start counter. - ● ●
AI, 16 Pump2 start counter R Pump 2 start counter. - ● ●
AI, 17 Pump1 current R Pump 1 current in amperes. A ● ●
AI, 18 Pump2 current R Pump 2 current in amperes. A ● ●
AI, 19 Pump1 operating time R Pump 1 overall operating time in minutes. min ● ●
AI, 20 Pump2 operating time R Pump 2 overall operating time in minutes. min ● ●
AI, 21 UserAnalogInput1 R User-defined measurement, analog input 1. % ● ●
AI, 22 UserAnalogInput2 R User-defined measurement, analog input 2. % ● ●
AI, 23 UserAnalogInput3 R User-defined measurement, analog input 3. % ● ●
AI, 24 UserAnalogInput4 R User-defined measurement, analog input 4. % ● ●
AI, 25 UserAnalogInput5 R User-defined measurement, analog input 5. % ● ●
AI, 26 Last operating time pump1 R Last operating time for pump 1. s ● ●
AI, 27 Last operating time pump2 R Last operating time for pump 2. s ● ●
AI, 28 Energy consumption pump1 R Energy consumption pump 1. kWh ● ●
AI, 29 Energy consumption pump2 R Energy consumption pump 2. kWh ● ●
AI, 30 System Energy today R DATA_ENERGY_TODAY reported with 0.1 kWh resolution. kWh - ●
AI, 31 PulseFlowMeter R DATA_PULSE_FLOW_METER l/s ● ●
AI, 32 Turbidity R DATA_TURBIDITY reported with 0.1 NTU resolution. NTU ● ●
AI, 33 PhMeasure R DATA_PH_MEASURE reported with 0.1 pH resolution. pH ● ●
AI, 34 Conductivity R DATA_CONDUCTIVITY reported with 1 S/m resolution. S/m ● ●
AI, 35 Pump1OprTimeToday R DATA_PUMP1_RUNTIME_TODAY min - ●
AI, 36 Pump2OprTimeToday R DATA_PUMP2_RUNTIME_TODAY min - ●
AI, 37 Pump1StartCounterToday R DATA_PUMP1_RUNTIME_TODAY min - ●
AI, 38 Pump2StartCounterToday R DATA_PUMP2_RUNTIME_TODAY min - ●
AI, 39 Alarms 1-5 and warnings 1-5 R
Values are transmitted in the following order:
• bit 0: Status warning 1
• bit 1: Status warning 2
• bit 2: Status warning 3
• bit 3: Status warning 4
• bit 4: Status warning 5
• bit 8: Status alarm 1
• bit 9: Status alarm 2
• bit 10: Status alarm 3
• bit 11: Status alarm 4
• bit 12: Status alarm 5
Bit values indicate the following:
• bit value 0: Alarm or warning not present
• bit value 1: Alarm or warning present
- ● ●
18