EasyManua.ls Logo

Grundfos MGE 71 - FM 200 Terminal Connections

Grundfos MGE 71
38 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
English (GB)
11
* If an external supply source is used, there must be a
connection to GND.
Fig. 11 Connection terminals, FM 200
TM05 3510 3512
Terminal Type Function
NC
Normally closed
contact
Signal relay 1
(LIVE or SELV)
C1 Common
NO
Normally open
contact
NC
Normally closed
contact
Signal relay 2
(SELV only)
C2 Common
NO
Normally open
contact
10 DI3/OC1
Digital input/output,
configurable.
Open collector: Max. 24 V
resistive or inductive.
4AI1
Analog input:
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
2 DI1 Digital input, configurable
5+5 V
Supply to potentiometer and
sensor
6 GND Ground
A GENIbus, A GENIbus, A (+)
Y GENIbus, Y GENIbus, GND
B GENIbus, B GENIbus, B (-)
3 GND Ground
15 +24 V Supply
8 +24 V Supply
26 +5 V
Supply to potentiometer and
sensor
23 GND Ground
25 GDS TX
Grundfos Digital Sensor
output
24 GDS RX Grundfos Digital Sensor input
7AI2
Analog input:
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V

Other manuals for Grundfos MGE 71

Related product manuals