English (GB)
20
Warning
In case of a warning, the cause will appear in this display together
with a fault code.
Possible warnings:
A warning indication will disappear automatically once the fault
has been remedied.
Alarm log 1 to 5
In case of "alarm" faults, the last five alarm indications will appear
in the alarm log. "Alarm log 1" shows the latest fault, "Alarm log 2"
shows the latest fault but one, etc.
The example above gives this information:
• The alarm indication "Other fault".
• The fault code "(73)".
• The number of minutes the motor has been connected to the
power supply after the fault occurred.
Warning log 1 to 5
In case of "warning" faults, the last five warning indications will
appear in the warning log. "Warning log 1" shows the latest fault,
"Warning log 2" shows the latest fault but one, etc.
The example above gives this information:
• The warning indication "Replace motor bearings".
• The fault code "(30)".
• The number of minutes the motor has been connected to the
power supply after the fault occurred.
8.4.3 STATUS menu
The displays appearing in this menu are status displays only. It is
not possible to change or set values.
The displayed values are the values that applied when the last
communication between the motor and the R100 took place. If a
status value is to be updated, point the R100 at the control panel
and press [OK].
If a parameter, for example speed, should be called up
continuously, press [OK] constantly during the period in which the
parameter in question should be monitored.
The tolerance of the displayed value is stated under each display.
The tolerances are stated as a guide in % of the maximum values
of the parameters.
Actual setpoint and external setpoint
Tolerance: ± 2 %
This display shows the actual setpoint and the external setpoint in
% of the range from minimum value of sensor measuring range to
the setpoint set.
At a min. speed of 12 %, a set setpoint of 65 % and an external
setpoint of 70 %, the actual setpoint will be
0.70 x (65 - 12) + 12 = 49 %.
Operating mode
This display shows the actual operating mode (Stop, Min., Normal
(duty), Max. or Manual (operation)). Furthermore, it shows where
this operating mode was selected (Handheld, Motor, Bus,
External or Start/stop button).
Actual controlled value
The actual controlled value will appear in this display if a sensor
has been connected and the function of the analog input has
been set to "Feedback sensor".
See section Analog input 1, 2 and 3, Function, page 24.
Warning Fault code
No contact to pump 10
Internal fault 83, 85, 163
Electronics temperature too high 66
Sensor signal outside signal range 88
Sensor supply fault, 5 V 161
Sensor supply fault, 24 V 162
Too high motor temperature 65
Signal outside range, analog input 1 165
Signal outside range, analog input 2 166
Signal outside range, analog input 3 167
Temperature sensor 1 outside signal range 91
Temperature sensor 2 outside signal range 175
Limit 1 exceeded 190
Limit 2 exceeded 191
Replace motor bearings 30