5.4.5 Menus
There are two menus in the controller:
settings menu
information menu
Settings menu
Menu Designation Description
L_01 Start level Set the start level in this menu.
I_02 Rated current Set the rated current.
T_01 Stop delay Set a stop delay for the pumps.
T_02 Start delay Set a start delay for the
pumps.
T_03 Alarm delay Set an alarm delay for the sys-
tem.
M_01 Maintenance interval Set the maintenance interval to
0, 3, 6 or 12 months. To disa-
ble the function, set the interval
to 0 months.
A_01 Resetting of alarms Select manual or automatic re-
setting of alarms.
G_01 Resetting to factory settings -
Exit Exit Go back to the main menu.
Information menu
Menu Designation Description
F_01 Fault log The fault log shows the latest
20 faults.
R_01 Hours counter [h] The hours counter shows the
number of operating hours.
R_02 Impulse counter The impulse counter shows the
number of starts.
R_03 Motor current [A] The motor current is the aver-
age of the last 20 measure-
ments.
Exit Exit Go back to the main menu.
5.4.6 Factory settings
Function Factory setting
Start level Not set from factory.
Rated current Not set from factory; to be set according to the motor nameplate.
Stop delay 1 second
Start delay 0 seconds
Alarm delay 5 seconds
Maintenance interval 0 months
Multilift MD1, MDV | | 23