EasyManua.ls Logo

Grundfos RMQ A Series - Connection of Mains-Water Pipe

Grundfos RMQ A Series
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
English (GB)
7
3. Before fitting a bend, if required, check that the
DN 70 pipe has a vertical fall of minimum 50 cm.
Connect the overflow to the sewage system via a
vented pipe.
Fig. 4 Overflow to sewer, example 1
Fig. 5 Overflow to sewer, example 2
8.4 Connection of mains-water pipe
The built-in float valve is designed for a maximum
pressure of 6.0 bar.
The float valve has a simple filter in the inlet. If the
mains water is particularly dirty, we recommend that
you fit a strainer in front of the inlet to the float valve.
Fig. 6 Filter in the inlet
We recommend that you fit an isolating valve in the
fixed installation.
Procedure:
1. Connect the mains-water pipe to the mains-water
hose of the unit. See fig. 1 (4).
2. Fasten the mains-water pipe with pipe clamps.
The first hose clamp must be fitted at a maximum
distance of 10-15 cm from the unit.
3. Check that the float valve is positioned straight in
the mains-water tank. See fig. 7.
– The float valve must be able to move freely up
and down without touching the sides of the
tank.
Fig. 7 The float valve seen from above
The RMQ overflow does not function as a
water seal.
TM04 7634 2210
Pos. Description
1 Vent cap
2 Water seal
TM04 7633 2210
1
2
Min. 0.5 m
Min. 0.5 m
TM04 6914 1110
Do not push or pull the mains-water hose;
otherwise it may cause failure of the float
valve.
TM04 6915 1110

Related product manuals