Interval 2:
P3.12.2.1: ON Time: 09:00:00
P3.12.2.2: OFF Time: 13:00:00
P3.12.2.3: Days: Saturday, Sunday
P3.12.2.4: AssignToChannel: Time channel 1
Timer 1
The manual bypassing can be handled by a digital
input 1 on slot A (by a different switch or connection
to lighting).
P3.12.6.1: Duration: 1800 s (30 min)
P3.12.6.3: Assign to channel: Time channel 1
P3.12.6.2: Timer 1: DigIn SlotA.1 (Parameter located
in digital inputs menu.)
Finally select the Channel 1 for the I/O Run
command.
P3.5.1.1: Control signal 1 A: Time Channel 1
9136
Final configuration where Time channel 1 is used as control signal for start command instead of a digital input
Pos. Description
1 Interval 1
2 Days = Monday to Friday
3 ON = 07.00.00 hrs OFF = 17.00.00 hrs
4 Interval 2
5 Days = Saturday and Sunday
6 ON = 09.00.00 hrs OFF = 13.00.00 hrs
7 Digital input 1 on Slot A
8
Timer 1
Duration = 1800 s
9 Ctrl Signal 1A
10 Time channel 1
11 Start/Stop
106
English (GB)