4.9 Power ratings
AC drive (208-240 V 3AC 50/60 Hz, up to 400 V DC) output ratings
Enclosure
size
AC drive
type
Voltage
(nominal
or range)
[V AC]
Current
(maximu
m
continuou
s)
[A AC]
Current
(inrush)
[A AC]
(2 s)
Frequenc
y
(nominal
or range)
[Hz]
Power
(maximu
m
continuou
s)
[W]
(230 V)
Power
factor
range
Max.
output
fault
current
[A AC]
Max.
output
over
current
protection
[A AC]
A
0006 0-240 6.6 13.2 0-320 1100 0.3-1 19.9 19.9
0008 0-240 8.0 16.0 0-320 1500 0.3-1 26.3 26.3
0011 0-240 11.0 22.0 0-320 2200 0.3-1 33.1 33.1
0012 0-240 12.5 25.0 0-320 3000 0.3-1 39.8 39.8
B
0018 0-240 18.0 36.0 0-320 4000 0.3-1 72.3 72.3
0024 0-240 24.2 48.4 0-320 5500 0.3-1 72.3 72.3
0031 0-240 31.0 62.0 0-320 7500 0.3-1 91.1 91.1
C
0048 0-240 48.0 96.0 0-320 11000 0.3-1 154.3 154.3
0062 0-240 62.0 124.0 0-320 15000 0.3-1 185.7 185.7
MR5
0018 0-240 18.0 25.0 0-320 4000 0.3-1 50.0 50.0
0024 0-240 24.0 36.0 0-320 5500 0.3-1 72.0 72.0
0031 0-240 31.0 46.0 0-320 7500 0.3-1 100.0 100.0
MR6
0048 0-240 48.0 62.0 0-320 11000 0.3-1 124.0 124.0
0062 0-240 62.0 96.0 0-320 15000 0.3-1 192.0 192.0
MR7
0075 0-240 75.0 124.0 0-320 18500 0.3-1 248.0 248.0
0088 0-240 88.0 150.0 0-320 22000 0.3-1 300.0 300.0
0105 0-240 105.0 176.0 0-320 30000 0.3-1 352.0 352.0
MR8
0140 0-240 140.0 210.0 0-320 37000 0.3-1 456.0 456.0
0170 0-240 170.0 280.0 0-320 45000 0.3-1 560.0 560.0
0205 0-240 205.0 340.0 0-320 55000 0.3-1 680.0 680.0
MR9A
0261 0-240 261.0 410.0 0-320 75000 0.3-1 844.0 844.0
0310 0-240 310.0 502.0 0-320 90000 0.3-1 1004.0 1004.0