Group 3.13.3: Feedbacks
Code Parameter Min Max Unit Default ID Description
P3.13.3.1 Function 1 9 1 333
1 = Only Source1 in use
2 = SQRT (Source1); (Flow = Constant x
SQRT (Pressure))
3 = SQRT (Source1- Source 2)
4 = SQRT (Source 1) + SQRT (Source 2)
5 = Source 1 + Source 2
6 = Source 1 - Source 2
7 = MIN (Source 1, Source 2)
8 = MAX (Source 1, Source 2)
9 = MEAN (Source 1, Source 2)
P3.13.3.2 Gain -1000.0 1000.0 % 100.0 1058
Used e.g. with selection 2 in Feedback
function
P3.13.3.3 FB 1 Source 0 20 2 334
0 = Not used
1 = AI1
2 = AI2
3 = AI3
4 = AI4
5 = AI5
6 = AI6
7 = ProcessDataIn1
8 = ProcessDataIn2
9 = ProcessDataIn3
10 = ProcessDataIn4
11 = ProcessDataIn5
12 = ProcessDataIn6
13 = ProcessDataIn7
14 = ProcessDataIn8
15 = Temperature input 1
16 = Temperature input 2
17 = Temperature input 3
18 = Temperature input 4
19 = Temperature input 5
20 = Temperature input 6
AI's and ProcessDataIn are handled as %
(0.00-100.00 %) and scaled according to
Feedback min and max.
Note: ProcessDataIn use two decimals.
P3.13.3.4 FB 1 Minimum -200.00 200.00 % 0.00 336
Minimum value at analogue signal
minimum.
P3.13.3.5 FB 1 Maximum -200.00 200.00 % 100.00 337
Maximum value at analogue signal
maximum.
P3.13.3.6 FB 2 Source 0 20 0 335 See P3.13.3.3
P3.13.3.7 FB 2 Minimum -200.00 200.00 % 0.00 338
Minimum value at analogue signal
minimum.
P3.13.3.8 FB 2 Maximum -200.00 200.00 % 100.00 339
Maximum value at analogue signal
maximum.
111