8.2.12 Analog outputs
P3.5.4.1.1 AO1 function
This parameter defines the content of the analogue
output signal 1. The scaling of the analogue output
signal depends on the selected signal. See the table
below.
Selection Selection name Description
0 Test 0 % (Not used)
Analogue output is forced either to 0 % or 20 % depending on
parameter P3.5.4.1.3.
1 TEST 100 % Analogue output is forced to 100 % signal (10 V / 20 mA).
2 Output frequency Actual output frequency from zero to MaxFreqReference.
3 Frequency reference Actual frequency reference from zero to MaxFreqReference.
4 Motor speed Actual motor speed from zero to Motor Nom Speed.
5 Output current Drive output current from zero to Motor Nom Currnt.
6 Motor torque Actual motor torque from zero to motor nominal torque (100 %).
7 Motor power Actual motor power from zero to Motor Nom Power (100 %).
8 Motor voltage Actual motor voltage from zero to Motor Nom Voltg.
9 DC-link voltage Actual DC-link voltage 0…1000 V.
10 PID output PID controller output (0…100 %).
11 ExtPID output External PID controller output (0…100 %).
12 Fieldbus Process Data In 1
Fieldbus Process Data In 1 from 0…10000 (corresponding 0…100.00
%).
13 Fieldbus Process Data In 2
Fieldbus Process Data In 2 from 0…10000 (corresponding 0…100.00
%).
14 Fieldbus Process Data In 3
Fieldbus Process Data In 3 from 0…10000 (corresponding 0…100.00
%).
15 Fieldbus Process Data In 4
Fieldbus Process Data In 4 from 0…10000 (corresponding 0…100.00
%).
16 Fieldbus Process Data In 5
Fieldbus Process Data In 5 from 0…10000 (corresponding 0…100.00
%).
17 Fieldbus Process Data In 6
Fieldbus Process Data In 6 from 0…10000 (corresponding 0…100.00
%).
18 Fieldbus Process Data In 7
Fieldbus Process Data In 7 from 0…10000 (corresponding 0…100.00
%).
19 Fieldbus Process Data In 8
Fieldbus Process Data In 8 from 0…10000 (corresponding 0…100.00
%).