8.2.13 Prohibit Freq
P3.7.1 Range 1 Low Lim
P3.7.2 Range 1 High Lim
P3.7.3 Range 2 Low Lim
P3.7.4 Range 2 High Lim
P3.7.5 Range 3 Low Lim
P3.7.6 Range 3 High Lim
1
2
3
3
2
4
9118
Prohibited frequencies
Pos. Description
1 Actual reference
2 High Lim
3 Low Lim
4 Requested reference
P3.7.7 RampTimeFactor
The Ramp time factor defines the acceleration/
deceleration time when the output frequency is in a
prohibited frequency range. The Ramp time factor is
multiplied with the value of parameters P3.4.1.2/
P3.4.1.3 (Ramp acceleration/deceleration time). For
example the value 0.1 makes the acceleration/
deceleration time ten times shorter.
1
2
3
4
5
6
9211
Ramp time factor
Pos. Description
1 Output Frequency [Hz]
2 High Lim
3 Low Lim
4 Ramp Time Factor = 0.3
5 Ramp Time Factor = 2.5
6 Time [s]
149