8.2.21 Soft fill
P3.13.8.1 Enable
P3.13.8.2 SoftFill Freq
P3.13.8.3 SoftFill Level
P3.13.8.4 Timeout Time
The drive runs at the soft fill frequency (par.
P3.13.8.2) until the feedback value reaches the soft
fill level set parameter P3.13.8.3. After this the drive
starts to regulate, bump less, from the soft fill
frequency. If the soft fill level is not reached within the
timeout (P3.13.8.4) an alarm or fault is triggered
(according to the set Soft Fill timeout response
(P3.9.1.9)).
9105
Soft fill function
Pos. Description
1 Reference
2 Actual value
3 Soft fill level
4 Frequency
5 Soft fill frequency
6 Soft fill mode
7 Regulating mode
8.2.22 Auto-Cleaning
P3.21.1.1 Clean Function
If Auto-cleaning function is enabled by parameter
P3.21.1.1 the Auto-cleaning sequence will start by
activating the digital input signal selected by
parameter P3.21.1.2.
P3.21.1.2 Clean Activation
See above.
P3.21.1.3 Clean Cycles
The Forward/reverse cycle will be repeated for the
amount of times defined by this parameter.
161
English (GB)