Code Parameter Min Max Unit Default ID Description
P1.34.5 SP 1 Source 0 22 1 332
0 = Not used
1 = Keypad setpoint 1
2 = Keypad setpoint 2
3 = AI1
4 = AI2
5 = AI3
6 = AI4
7 = AI5
8 = AI6
9 = ProcessDataIn1
10 = ProcessDataIn2
11 = ProcessDataIn3
12 = ProcessDataIn4
13 = ProcessDataIn5
14 = ProcessDataIn6
15 = ProcessDataIn7
16 = ProcessDataIn8
17 = Temperature input 1
18 = Temperature input 2
19 = Temperature input 3
20 = Temperature input 4
21 = Temperature input 5
22 = Temperature input 6
AI's and ProcessDataIn are handled as
percent (0.00-100.00 %) and scaled
according to Setpoint minimum and
maximum.
Note: ProcessDataIn signals use 2
decimals.
P1.34.6
Keypad SP 1 Varies Varies Varies 0 167
P1.34.7 SP 1 Sleep Freq 0.00 320.00 Hz 0.00 1016
Drive goes to sleep mode when the
output frequency stays below this limit
for a time greater than that defined by
parameter Sleep Delay.
P1.34.8 SP 1 Sleep Delay 0 3000 s 0 1017
The minimum amount of time the
frequency has to remain below the Sleep
level before the drive is stopped.
P1.34.9
SP 1
WakeUpLevel
Varies 0.00 1018
Defines the level for the PID feedback
value wake-up supervision. Uses
selected process units.
P1.34.10 Preset Freq 1 P1.3 P1.4 Hz 10.0 105 Preset Freq 1