The Trend Curve feature also allows you to halt the
progression of the curve and read the exact individual
values.
1. In Trend curve view, select the display with the
arrow button up (the frame of the display turns
bold) and press OK at the desired point of the
progressing curve. A vertical hairline appears on
the display.
2. The display freezes and the values at the bottom
of the display correspond to the location of the
hairline.
3. Use the arrow buttons left and right to move the
hairline to see the exact values of some other
location.
OK
TM078685
Code Parameter Min Max Unit Default ID Description
M2.2.1 View Trend curve
Enter this menu to select and monitor
values for viewing in curve form.
P2.2.2 Sampling interval 100 432000 ms 100 2368 Set here the sampling interval.
P2.2.3 Channel 1 min -214748 1000 -1000 2369
Used by default for scaling. Adjustments
might be necessary.
P2.2.4 Channel 1 max -1000 214748 1000 2370
Used by default for scaling. Adjustments
might be necessary.
P2.2.5 Channel 2 min -214748 1000 -1000 2371
Used by default for scaling. Adjustments
might be necessary.
P2.2.6 Channel 2 max -1000 214748 1000 2372
Used by default for scaling. Adjustments
might be necessary.
P2.2.7 Autoscale 0 1 0 2373
The selected signal is automatically scaled
between min and max values if this
parameter is given value 1.