10. Setting the product
The pump will remember the controller settings even if it is turned
off.
10.1 Setting the outlet pressure
Adjust the outlet pressure by pressing .
10.2 Locking and unlocking the operating panel
The operating panel can be locked, which means that the buttons
do not function and no settings can be changed accidentally.
How to lock the operating panel
1. Hold down the buttons simultaneously for 3 seconds.
2. The operating panel is locked when
symbol lights up.
How to unlock the operating panel
1. Hold down the buttons simultaneously for 3 seconds.
2. The operating panel is unlocked when symbol turns off.
10.3 Expert settings, SCALA2
Expert settings are for installers only.
The expert setting menu allows the installer to toggle between the
following functions:
self-learning
auto reset
anti cycling
maximum continuous operating time.
10.3.1
Accessing the expert settings
Proceed as follows:
1. Hold down the
button for 5 seconds.
2.
The symbol will start flashing to indicate that the expert
settings are active.
The pressure indicator now acts as the expert menu. A flashing
green diode is the cursor. Move the cursor using the
buttons,
and toggle the selection on or off using the
button. The diode for
each setting will light up when the setting is active.
Move cursor up.
Move cursor down.
Toggle settings.
5
1
2
3
4
TM064346
Expert menu overview
Pos. Description
1 Auto reset
2 Anti cycling
3 Maximum continuous operating time
4 Exit expert menu
5 Self-learning
17
English (GB)

Other manuals for Grundfos SCALA2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Grundfos SCALA2 and is the answer not in the manual?

Grundfos SCALA2 Specifications

General IconGeneral
Max Inlet Pressure6 bar
Pumped LiquidClean water
Maximum Operating Pressure10 bar
InstallationIndoor
Mains Frequency50/60 Hz
Connection Size1 inch
Pump TypeSelf-priming, centrifugal pump
Max Flow3 m³/h
Power Supply1 x 200-240 V
Power Consumption550 W
Liquid Temperature Range0°C to +45°C
Protection ClassX4D
Weight10 kg
ApprovalsCE, EAC
Maximum Ambient Temperature+55°C
Type of Inlet ConnectionG 1 inch
Type of Outlet ConnectionG 1 inch
MaterialStainless steel