EasyManua.ls Logo

Grundfos TPE - Control Settings and Outputs; Controller Tuning and Relay Outputs

Grundfos TPE
42 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
English (GB)
26
10.9 Relay outputs
The pump incorporates two signal relays for potential-free
signalling. See section 17. Signal relays for further information.
The signal relays can be configured to be activated by one of the
following incidents:
Ready
Operation
Alarm
Warning
Limit 1 exceeded
Limit 2 exceeded
Pump running
Control of external fan
Not active.
10.10 Analog output
Whether the analog output is available or not, depends on the
functional module fitted in the pump:
To set up the analog output, make the settings below.
Output signal
0-10 V
0-20 mA
4-20 mA.
Function of analog output
Actual speed
Actual value
Resulting setpoint
Motor load
Motor current
Limit 1 exceeded
Limit 2 exceeded
Flow rate.
10.11 Controller settings
The pumps have a factory default setting of gain (K
p
) and integral
time (T
i
).
However, if the factory setting is not the optimum setting, the gain
and the integral time can be changed:
Set the gain (K
p
) within the range from 0.1 to 20.
Set the integral-action time (T
i
) within the range from 0.1 to
3600 s.
If 3600 s is selected, the controller will function as a P
controller.
Furthermore, the controller can be set to inverse control.
This means that if the setpoint is increased, the speed will be
reduced. In the case of inverse control, the gain (K
p
) must be set
within the range from -0.1 to -20.
Guidelines for setting of PI controller
The tables below show the recommended controller settings:
L1 = Distance [m] between pump and sensor.
1)
In heating systems, an increase in pump performance will
result in a rise in temperature at the sensor.
2)
In cooling systems, an increase in pump performance will
result in a drop in temperature at the sensor.
L2 = Distance [m] between heat exchanger and sensor.
Function (terminal)
FM 200
(standard)
FM 300
(advanced)
Relay output 1 (NC, C1, NO) ●●
Relay output 2 (NC, C2, NO) ●●
Function (terminal)
FM 200
(standard)
FM 300
(advanced)
Analog output -
Differential-pressure
control
K
p
T
i
0.5 0.5
0.5
L1 < 5 m: 0.5
L1 > 5 m: 3
L1 > 10 m: 5
Temperature control
K
p
T
i
Heating
system
1)
Cooling
system
2)
0.5 -0.5 10 + 5L2
0.5 -0.5 30 + 5L2
p
p
p
p
ǻS
L1
L1
ǻS
L2
t
L2
t

Table of Contents

Related product manuals