English (GB)
38
Analog output (AO)
Current sourcing capability only.
Voltage signal:
• Range: 0-10 VDC.
• Minimum load between AO and GND: 1 kΩ.
• Short-circuit protection: Yes.
Current signal:
• Ranges: 0-20 and 4-20 mADC.
• Maximum load between AO and GND: 500 Ω.
• Open-circuit protection: Yes.
Tolerance: - 0/+ 4 % of full scale (max-point coverage).
Screened cable: 0.5 - 1.5 mm
2
/ 28-16 AWG.
Maximum cable length: 500 m.
Pt100/1000 inputs (PT)
Temperature range:
• Minimum -30 °C (88 Ω/882 Ω).
• Maximum +180 °C (168 Ω/1685 Ω).
Measurement tolerance: ± 1.5 °C.
Measurement resolution: < 0.3 °C.
Automatic range detection (Pt100 or Pt1000): Yes.
Sensor fault alarm: Yes.
Screened cable: 0.5 - 1.5 mm
2
/ 28-16 AWG.
Use Pt100 for short wires.
Use Pt1000 for long wires.
LiqTec sensor inputs*
Use Grundfos LiqTec sensor only.
Screened cable: 0.5 - 1.5 mm
2
/ 28-16 AWG.
Grundfos Digital Sensor input and output (GDS)*
Use Grundfos Digital Sensor only.
* Not applicable for TPE, TPED, NKE, NKGE, NBE and NBGE
pumps.
Power supplies (+5 V, +24 V)
+5 V:
• Output voltage: 5 VDC - 5 %/+ 5 %.
• Maximum current: 50 mADC (sourcing only).
• Overload protection: Yes.
+24 V:
• Output voltage: 24 VDC - 5 %/+ 5 %.
• Maximum current: 60 mADC (sourcing only).
• Overload protection: Yes.
Digital outputs (relays)
Potential-free changeover contacts.
Minimum contact load when in use: 5 VDC, 10 mA.
Screened cable: 0.5 - 2.5 mm
2
/ 28-12 AWG.
Maximum cable length: 500 m.
Bus input
Grundfos GENIbus protocol, RS-485.
Screened 3-core cable: 0.5 - 1.5 mm
2
/ 28-16 AWG.
Maximum cable length: 500 m.
22. Other technical data
EMC (electromagnetic compatibility)
EN 61800-3.
Residential areas, unlimited distribution, corresponding to
CISPR 11, class B, group 1.
Industrial areas, unlimited distribution, corresponding to
CISPR 11, class A, group 1.
Contact Grundfos for further information.
Enclosure class
Standard: IP55 (IEC 34-5).
Optional: IP66 (IEC 34-5).
Insulation class
F (IEC 85).
22.1 Torques
22.2 Sound pressure level
The grey fields indicate that the motor is not yet available in this
MGE motor range, but is available in the previous MGE motor
range.
23. Disposal
This product or parts of it must be disposed of in an
environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company
or service workshop.
The waste battery should be disposed of through the national
collective schemes. If in doubt, contact your local Grundfos
company.
Subject to alterations.
Terminal Thread size
Max. torque
[Nm]
L1, L2, L3, L, N M4 1.8
NC, C1, C2, NO M2.5 0.5
1 to 26 and A, Y, B M2 0.5
Motor
[kW]
Max. speed
stated on
nameplate
[min
-1
]
Speed
[min
-1
]
Sound pressure level
ISO 3743
[dB(A)]
1-phase
motors
3-phase
motors
0.12 to
0.75
2000
1500 38 38
2000 42 42
4000
3000 53 53
4000 58 58
1.1
2000
1500
38
2000
42
4000
3000 53 53
4000 58 58
1.5 4000
3000 57 57
4000 64 64
2.2 4000
3000
57
4000
64