GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 21
The following steps show how to operate the DISABLE button.
1. Enter access level II as described in Section 3.1.2.
2. First, pressing the SILENCE/RESOUND ALARM button silences the sounder output when any
zone is in fire condition.
3. Pressing the DISABLE button, DISABLE LED illuminates steadily and the amber LEDs of all
zones in fire condition illuminate.
4. Exit access level II.
The following steps show how to operate the DIS/ENABLE WARNING SYSTEM button.
1. Enter access level II.
2. Pressing the DIS/ENABLE WARNING SYSTEM button, DISABLE LED and SOUNDER X
FLT/DIS LED illuminate steadily and all sounder outputs are disabled. The CIE will give 1s
sound indication.
3. Pressing the DIS/ENABLE WARNING SYSTEM key again, SOUNDER X FLT/DIS LED turns
off. DISABLE LED also turns off if there is no other disablement event. The CIE will give 1
second sound indication.
4. Exit access level II.
3.4 Setting Test Mode
3.4.1 Use of Test Mode
Test mode is for testing that the detection zones operate correctly. In this mode, it tests if a zone
can generate a fire alarm signal when it’s manually activated into fire condition, Alarm Output will
not be activated, and sounder outputs can be programmed to either output for 10 seconds or no
output (refer section 3.7 for details).
☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆
Note: Test mode cannot be saved even if the CIE is powered off.
Note: The reset operation can restore the fire in test mode.
☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆
3.4.2 Operation Steps
1 Enter access Level II.
2 Pressing the TEST button, TEST LED illuminates steadily. The amber LED of zone 1 starts
flashing, showing the CIE is in test mode and that zone 1 is selected. The FAULT LED will
indicate according to the CIE fault condition. Other indicators, except for the above mentioned
LEDs, will be turned off.
3 Pressing the SCROLL button will toggle between zones 1 to 16.
4 Zone amber LED for zone 1 to 16 will flash when the zone is to be selected. Pressing the
ENTER button to set the zone to test mode. The illuminating IN TEST LED indicates the zone
is in test mode.
5 Pressing the ENTER button can change the zone is defined as test zone or not and the CIE
will give 1 second sound indication.
6 Pressing the CANCEL button exits test mode setting status and TEST LED turns off.
7 Exit access Level II.