2
-1. General
Main supply
: 115V/230V±15% 50/60Hz (Switch selectable).
Rating, dimension and weight : See Table 2-1.
Table 2-1
MAX. RATING INPUT RATING FUSE STYLE & RATING WEIGHT
Model
Voltage
Current
Watts VA 115V 230V kg
SPS-1820
18V 20A 500 900 T 10A 250V
T 6.3A 250V
3.3
SPS-3610
36V 10A 500 900 T 10A 250V
T 6.3A 250V
3.3
SPS-606 60V 6A 500 900 T 10A 250V
T 6.3A 250V
3.3
Dimensions:128(W) × 145(H) × 285(D) mm.
WARNING: Voltage over 60V DC is a lethal shock hazard to the user. Be careful when
connecting power supplies in series to achieve voltage higher than 60V DC totally or 60V DC
between any connection and earth ground.
Operation Environment : Indoor use,
Altitude up to 2000m,
Installation Category II,
Pollution degree 2.
Operation Temperature &Humidity
: 0℃ to 40℃, <80%.
Storage Temperature & Humidity : -10℃ to 70℃, <70%.
Accessories : Test Lead (current < 4A)…………………………………………… × 1
Operation Manual ..………………………………………………………… × 1
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com