- 34 -
3
unit No.
setting by
wired
controller
1. “1” of SW03 at “ON” (up)
2. press “filter reset” button for 5 seconds
then enter system address setting mode,
choose indoor address by press ”TEMP+
/-” button.
3. Temp. display area displays: system
address+XX, then press ”TEMP+/-”
button, the unit No. will change within
00~3F( 00 is No 1 unit, 3F is No.64
unit) ,original value is 00.
4. after the No. of unit is chosen, press
“SET” button to save all the settings. If
you press the other buttons, or no any
actions within 15 seconds, then the
setting will exit automatically and system
will keep the setting of last time.
setting
on site
Communication address between indoor and outdoor ( setting by hand)
Unit No. setting by hand
(dip switch position of SW03 is in correspondence with the marks on
PCB)
SW03 SW03
1 2 3 4 5 6 7 8
Indoor
addres
s
1 2 3 4 5 6 7 8
Indoor
addre
ss
0 0 0 0 0 0 1 1 0 0 0 0 0 33
0 0 0 0 0 1 2 1 0 0 0 0 1 34
0 0 0 0 1 0 3 1 0 0 0 1 0 35
0 0 0 0 1 1 4 1 0 0 0 1 1 36
0 0 0 1 0 0 5 1 0 0 1 0 0 37
0 0 0 1 0 1 6 1 0 0 1 0 1 38
0 0 0 1 1 0 7 1 0 0 1 1 0 39
1 1
0 0 0 1 1 1 8
11
1 0 0 1 1 1 40
Part 2