0010451181ACN10 terminal of EEV 6-core red
dip switch
state when
out of factory
jumper
state when
out of
factory
functions
SW06-1 ON J10 connected
0: fix air volume
1: commonly control
SW06-2 ON J7 connected
0/1 temp. difference
selection in AUTO mode
0: Tdif = 2
1: Tdif = 3
SW06-3 ON J6 connected
0without TA in AUTO mode
1: with TA correction value
SW06-4 ON J5
connected
standby
SW06-5 ON J4
connected
0: cooling only
1: heat pump
SW06-6 ON J3
connected
0: uniform control of temp.
correction
1: individual control
SW06-7 ON J2
connected
SW06-8 ON J1
connected
air inlet temp. correction
value:
(J1)0(J2)06ºC
(J1)0(J2)14ºC
(J1)1(J2)02ºC
(J1)1(J2)10ºC
SW07-1 ON J16
connected
SW07-2 ON J15
connected
standby
SW07-3 ON J14 connected
SW07-4 ON J13 connected
SW07-5 ON J12 connected
heat exchanging facto
r
selection(pre-set)
SW07-6
ON J11
connected
filter washing time selection
0120H
12500H