5.4.3 Outdoor running data display
SW
3
SW
4
SW
5
function
definition
content displayed on
digital tube
0/1/
2/3
0 0
display failure
code of the
outdoor
such as “20”, if no failure
it will shows “0”
0/1/
2/3
2 0
display running
mode of the
outdoor
“HHHH” means heating
“CCCC” means cooling
0/1/
2/3
3 0
display capacity of
the outdoor
such as “10” means 10
HP
0/1/
2/3
5 0
display running
frequency and
energy class of
the outdoor
such as “30” means
master unit running with
30Hz
eg.: “10.0” shows 100%
capacity of slave unit;
“6.0” shows 60%
capacity of slave unit
0 6 0
display fan speed
of the master
unit
such as “9”, fan speed
for slave unit can not
be displayed
the outdoor
four-way valve
state
LED1 display “1” means
open, ”0” means close
the outdoor
unloading valve
SV1 state
LED2 display “1” means
open, ”0” means close
the outdoor oil
equalization valve
SV2 state
LED3 display “1” means
open, ”0” means close
0/1/
2/3
8 0
the outdoor
spraying valve
SV3 state
LED4 display “1” means
open, ”0” means close
Part 2