35
Smart Power
Item Model ADH071M3ERG/1UH071N1ERG
Function Cooling Heating
Capacity kW 7.1(2.0~9.0) 8(2.0~10.0)
Sensible heat ratio 0.72 /
Total power input kW 2.03(0.4~4.0) 2.0(0.4~4.0)
Max. power input W 4000 4000
AEER or ACOP W/W 3.41 3.89
Dehumidifying capacity 10
-3
×m
3
/h 2.4
Power cable 4.0mm
2
Power source N, V, Hz 1, 220~240, 50/60
Running/Max. Running current A/A
8.8(2.0-17.5)/17.5 9.2(2.0-17.5)/17.5
Start current A 0.52
Circuit breaker A
Indoor
unit
Unit model (color)
Fan
Type×Number
Speed (H-M-L) r/min
Fan motor output/ input power kW
Air-ow (H-M-L) m
3
/h
External static pressure Pa
Heat
exchanger
Type/Diameter mm
1Ph,30A(from outdoor)
ADH071M3ERG
CENTRIFUGALX2
1050/950/850/750
0.27/0.2
1450/1200/950/700
25/37/50/70/90/100/110/120/130/150
Inner grooved pipe/φ7.0
Total area m
2
7.668
Dimension
External (L×W×H) mm×mm×mm 957/655/250
Package (L×W×H) mm×mm×mm 1170/860/340
Drainage pipe (material, I.D./O.D.) mm PVC 25/29
Controller (O-Optional, S-Standard)
Wired YR-E16A(O)/YR-E17(S)
Infrared YR-HBS01 (O)
Fresh air hole dimension mm 145
Electricity heater kW /
Sound power noise level (H) dB (A) 58
Sound pressure noise level (H) dB (A) 38/35/32
Weight (Net / Shipping) kg / kg 31.2/36.8
Piping
Refrigerant
Type / Charge g R410A/2500
Recharge quantity g/m 45
Pipe
Liquid mm 9.52
Gas mm 15.88
Max.pipe lengh without
charge refrigerant
20
Between
I.D&O.D
MAX.Drop m 30
MAX.Piping length m 50
Connecting method Flared
Cooling Pdesignc (kW): 7.1kW SEER/CLASS 6.3/A++
QCE(Annual electricity
consumption for cooling)kWh:
390
Heating
Average Pdesignh (-10°C) 6.0kW SCOP/CLASS
4.2/A+
QHE(Annual electricity
consumption for heating)kWh:
1982
Warmer Pdesignh (2°C) 6.5kW SCOP/CLASS
4.8/A++
1652
Colder Pdesignh (-22°C) / SCOP/CLASS
/
/
Tdesignh: -10°C Tbivalent: -10°C TOL: -15°C Elbu: 0
Max. cooling
condition
Indoor temperature: 32°C/23°C
Max. heating condition
Indoor temperature: 27°C/-°C
Outdoor temperature: 46°C/-°C Outdoor temperature: 24C/18C
Norminal condition:
Indoor temperature (cooling) : 27DB (°C)/19WB (°C) , Indoor temperature (heating) : 20DB (°C)
Outdoor temperature (cooling) : 35DB (°C)/24WB (°C) , Outdoor temperature (heating) : 7DB (°C)/6WB (°C)
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity
meter. It is a sound pressure noise level.