37
Smart Power
Item Model ADH105M1ERG/1UH105N1ERG
Function Cooling Heating
Capacity kW 10 (2.5~11) 10.4 (2.5~12)
Sensible heat ratio 0.72 /
Total power input kW 2.93(0.5~4.5) 2.97 (0.5~4.5)
Max. power input W 5000 5000
AEER or ACOP W/W 3.37 3.46
Dehumidifying capacity 10
-3
×m
3
/h 3.2
Power cable 4.0mm
2
Power source N, V, Hz 1, 220~240, 50/60
Running/Max. Running current A/A
13.3 (2.3-19.0) /21.0 13.5 (2.3-19.0) /21.0
Start current A 3
Circuit breaker A
Indoor
unit
Unit model (color)
Fan
Type×Number
Speed (H-M-L) r/min
Fan motor output/ input power kW
Air-ow (H-M-L) m
3
/h
External static pressure Pa
Heat
exchanger
Type/Diameter mm
1Ph
40A (from outdoor
ADH105M1ERG
CENTRIFUGALX3
1050/950/850
0.16/0.2
2000/1740/1380/1280
30-120
Inner grooved pipe/φ7.0
Total area m
2
/
Dimension
External (L×W×H) mm×mm×mm 1500/700/250
Package (L×W×H) mm×mm×mm 1710/865/320
Drainage pipe (material, I.D./O.D.) mm PVC 26/32
Controller (O-Optional, S-Standard)
Wired YR-E16A(O)/YR-E17(S)
Infrared YR-HBS01 (O)
Fresh air hole dimension mm 100
Electricity heater kW /
Sound power noise level (H) dB (A) 55
Sound pressure noise level (H) dB (A) 32/28/25/23
Weight (Net / Shipping) kg / kg 49/61
Piping
Refrigerant
Type / Charge g R410A/2500
Recharge quantity g/m 45
Pipe
Liquid mm 9.52
Gas mm 15.88
Max.pipe lengh without
charge refrigerant
20
Between
I.D&O.D
MAX.Drop m 30
MAX.Piping length m 50
Connecting method Flared
Cooling Pdesignc (kW): 10kW SEER/CLASS 6.7/A++
QCE(Annual electricity
consumption for cooling)kWh:
548
Heating
Average Pdesignh (-10°C) 9.7kW SCOP/CLASS
4.0/A+
QHE(Annual electricity
consumption for heating)kWh:
3624
Warmer Pdesignh (2°C) 10.2kW SCOP/CLASS
4.8/A++
2976
Colder Pdesignh (-22°C) / SCOP/CLASS
/
/
Tdesignh: -10°C Tbivalent: -10°C TOL: -15°C Elbu: 0
Max. cooling
condition
Indoor temperature: 32°C/23°C
Max. heating condition
Indoor temperature: 27°C/-°C
Outdoor temperature: 46°C/-°C Outdoor temperature: 24C/18C
Norminal condition:
Indoor temperature (cooling) : 27DB (°C)/19WB (°C) , Indoor temperature (heating) : 20DB (°C)
Outdoor temperature (cooling) : 35DB (°C)/24WB (°C) , Outdoor temperature (heating) : 7DB (°C)/6WB (°C)
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity
meter. It is a sound pressure noise level.