6.2 Parts and Functions
ADH071M1ERG
ADH105M1ERG ADH125M1ERG ADH140M1ERG
ADH071M3ERG ADH090M1ERG
For AD105/125/140M1ERG,ADH071M3ERG, static pressure level selection can also be achieved by Infrared
remote controller,method is:
Step a: set the Infrared remote controller at condition: FAN mode, fan speed high.
Step b: then aim the remote controller at the infrared remote receiver RE-02, press HEALTH button 4+N
times(1≤N≤10,integer) within 12 seconds, then the receiver will beep N+1 times,the static pressure level N is been
set successfully.
Note: For Infrared remote controller YR-HBS01, need press ON/OFF button make the controller's at OFF status
rst, then open the button cover press FRESH button will enter FAN mode interface.
Static pressure level ( N)
External static pressure (pa)
ADH071M3ERG
ADH105M1ERG ADH125M1ERG
ADH140M1ERG
1 25 30
2 37 40
3 50 50
4 70 60
5 90 70
6 100 80
7 110 90
8 120 100
9 130 110
10 150 120