Super Match
Item Model
AD12MS1ERA
Function
cooling heating
Capacity KW
3.50(0.9~4.5) 4.00(1~4.8)
Sensible heat ratio
/ /
Total power input KW
1.08(0.28~1.8) 1.08(0.28~1.8)
Max. power input W
1800 1800
EER or COP W/W
3.23 3.71
Dehumidifying capacity 10
-
³×m³/h
1.6
Power cable
H05RN-F 4G 4.0mm2
Power source N, V, Hz
1PH, 220-230V~, 50/60Hz
Running /Max.Running current A / A
4.8(1.2-8.0)/8.0 5.6(1.2-8.0)/8.0
Start Current A
3
Circuit breaker A / /
Indoor unit
Unit model (color)
AD12MS1ERA
Fan
Type × Number
CENTRIFUGALX1
Speed(H-M-L) r/min
700/630/570
Fan motor output/ input power W
140/105
Air-ow(H-M-L) m³/h
550/460/400
ESP pa
10/30/50/70
Heat
exchanger
Type / Diameter mm
inner grooved pipe/φ7.0
Row
2
Total Area
/
Dimension
External(L×W×H) mm×mm×mm
750/720/250
Package(L×W×H) mm×mm×mm
920/820/340
Drainage pipe (material , I.D./O.D.) mm
PVC 25/29
Controller
(O-Optional,S-Standard)
Wired
YR-E14
S)/YR-E16(O)
Infrared
YR-HD01(O)
Fresh air hole dimension mm
145
Electricity Heater kW
NONE
Sound power Noise level (H-M-L) dB(A)
46/43/39
Sound pressure Noise level (H-M-L) dB(A)
36/33/29
Pipe
Liquid Pipe(mm)
6.35
Gas Pipe(mm)
9.52
Connecting Method
ared
Weight (Net / Shipping) kg / kg
22.8/27
33

Table of Contents