What to do if the switch stays ON and the motor keeps running on my HALE ESP Primer System Control Unit?
- DdillonjenniferAug 3, 2025
If the switch on your HALE Control Unit stays ON and the motor keeps running, first, ensure that cables aren't touching each other or other objects. Check cables for defects like fraying, splits, or corrosion, and repair or replace them as needed. Verify that each cable is tight and torqued to specifications. Use a VOM to check the solenoid for proper operation; it should open and close with the control switch. If it doesn't, replace the solenoid. Also, ensure proper voltage (minimum of 9.0VDC for 12VDC systems, 18.0VDC for 24VDC systems).