Why is there water downstream of my HANKISON Dehumidifier?
- AAshley ThomasAug 3, 2025
If you find water downstream of your HANKISON Dehumidifier, it could be due to several reasons. Residual free moisture might be present in the downstream pipelines, in which case you should blow out the system with dry air. Also, check the valve positions to ensure the air bypass system isn't open. Verify that the inlet and outlet connections are correctly connected. If air lines downstream are exposed to temperatures below the dew point, insulate or heat trace them, or use dry air to lower the dew point. If there's excessive free moisture at the dryer inlet, install a separator ahead of the dryer. If the condensate is not being drained, or the dryer is overloaded, or the refrigeration system isn't functioning, see section C for more details.