Output group
Output signal
Output operation
Cycle time
Cycle time of cooling output
Hysteresis of univesal type
Hysterecis of Heating /
Cooling type
Output volume when input
disconnection Output 1(Out1)
Output volume when input
disconnection Output 2(Out2)
Maximum value
Minimum value
Output code
(O T)
0
1
2
3
OUT2OUT1
Always
Output code
1 ~ 3
Relay / SSR
Output code
4 ~ 12
ON/OFF
Control
Heating
/ Cooling
Always
Heating /
Cooling
PID Control
PID Control
(3 / 12)
REV
30 sec
30 sec
EUS
(0.5 %)
0.5 %
0.0 %
0.0 %
100.0 %
0.0 %
100.0%
OUTPUT GROUP SETTING
Initial value
ConditionDescriptionNameSignal
Output type and mode selection
Refor to type of control output
REV: Reverse DIR: Direct action
1 ~ 1000 sec
1 ~ 1000 sec
EUS (0.0 ~ 100.0 %)
0.0 ~ 10.0 %
Universal : -5.0 ~ 105.0 %
Heating / Cooling : 0.0 ~ 105.0 %
0.0 ~ 105.0 %
Universal : OL-L + 1Digit~105.0%
Heating / Cooling : 0.0 ~ 105.0 %
Universal : -0.5 % ~ OL-H-1Digit
Heating / Cooling : 0.0 ~ 105.0 %
Relay
Relay ON / OFF
Relay
PX9-0
PX7-0
PX3-0
PX2-0
SSR / Current
SSR
Curren
Type of control output ( Universal type )
This process controller is divided into 2 types: UNIVERSAL TYPE AND HEATING / COOLING
TYPE. Output is selectable from Relay, SSR, and Current (4~20mA DC).
Output type range (output code) is
~ for universal type and ~ for Heating /Cooling type.
Sometimes retransmission output and alarm output are not available according to control output
(EX. When you choose output code (OT) 2, it is current output of Universal type. In this case,
retransmission output and alarm output are available. But, In Heating / Cooling control type with
SSR on Heating side and Relay output on Cooling side (output code
), the retransmission
output is avalable but alarm output 3 is not available.
Model
SSR / Current / Retransmission
Retransmission
Retransmission
Retransmission
Retransmission
13
When setting, “Input type selection number” must be selected in the input type selection
mode and also “Output type selection number” must be selected in the output type selection
mode before moving to other mode.If not, data of other group will be changed to prior value.
CAUTION
هرﮐ ﮓﻧﺎﯾﻧﺎھ تﻻوﺻﺣﻣ یرﺎﺻﺣﻧا هدﻧﯾﺎﻣﻧ ناوﯾﺳ تﮐرﺷ
021-33989001
www.sivancarno.com
021-33989002

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hanyoung PX2 series and is the answer not in the manual?

Hanyoung PX2 series Specifications

General IconGeneral
BrandHanyoung
ModelPX2 series
CategoryController
LanguageEnglish

Related product manuals