22
STD
OFF
Initial valueConditionDescriptionNameSignal
AUTO TUNING
Auto tuning group
Auto tuning type
Auto tuning start
Indicates Auto tuning
STD / LOW
OFF / 1~3 / AUTO
ABS
ABS
This controller has two types of auto-tuning as STD (Standard type) and LOW(Low PV type).
Low PV type is the value 10% lower than the set value. Use this type where overshoot is to be
suppressed.
Auto-tuning: The Auto-tuning function automatically measures, computes and set the optimum
P.I.D and ARW contants. The Auto-tuning function can be activated at any time
during the process after power ON; while temperature is rising or when control has
stabilized.
Auto tuning is not operated when selecting “OFF” in selection mode of auto tuning
start.
16