Design Guide HEV-HEH SEriES Heat Controller
12
12
Engineering Design Guide HEV/H SERIES Heat Controller, LLC
Performance Data
HEV/H 030 - Full Load
900 CFM Rated Air ow Performance capacities shown in thousands of Btuh
EWT
°F
GPM
WPD Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FT TC SC KW HR EER HWG HC KW HE LAT COP HWG
20
Operation Not
Recommended
Operation Not Recommended
Operation Not Recommended
7.5 5.7 13.3
21.8 1.9 15.2 89.2 3.3 2.7
30
3.8 2.3 5.2 35.3 21.8 1.4 40.1 25.3 1.3 23.5 2.0 16.7 90.9 3.5 2.8
5.6 3.5 8.1 35.7 22.0 1.3 40.2 27.3 1.1 24.5 2.0 17.6 91.8 3.6 2.9
7.5 5.1 11.8 35.8 22.0 1.3 40.1 28.3 1.0 25.0 2.0 18.0 92.3 3.6 2.9
40
3.8 1.7 4.0 34.5 21.5 1.5 39.7 22.6 1.7 26.6 2.1 19.5 93.8 3.7 3.0
5.6 2.9 6.6 35.1 21.7 1.4 40.0 24.5 1.4 27.7 2.1 20.5 94.9 3.8 3.1
7.5 4.3 10.0 35.4 21.8 1.4 40.1 25.5 1.3 28.3 2.1 21.0 95.5 3.9 3.2
50
3.8 1.2 2.8 33.5 21.0 1.7 39.2 20.0 2.2 29.7 2.2 22.3 96.9 4.0 3.3
5.6 2.2 5.1 34.2 21.4 1.6 39.6 21.8 1.8 31.0 2.2 23.5 98.2 4.1 3.5
7.5 3.5 8.1 34.6 21.5 1.5 39.8 22.8 1.7 31.7 2.2 24.1 98.9 4.2 3.5
60
3.8 1.2 2.7 32.1 20.5 1.8 38.4 17.5 2.9 32.9 2.3 25.1 100.0 4.2 3.7
5.6 2.0 4.6 33.1 20.9 1.7 38.9 19.2 2.4 34.4 2.3 26.5 101.4 4.4 3.9
7.5 3.3 7.6 33.5 21.1 1.7 39.2 20.1 2.2 35.2 2.3 27.2 102.2 4.4 4.0
70
3.8 1.1 2.5 30.7 19.9 2.0 37.6 15.1 3.7 36.0 2.4 28.0 103.0 4.5 4.1
5.6 1.9 4.5 31.7 20.3 1.9 38.1 16.7 3.1 37.7 2.4 29.4 104.6 4.6 4.4
7.5 3.1 7.2 32.2 20.5 1.8 38.4 17.6 2.9 38.6 2.4 30.2 105.5 4.6 4.5
80
3.8 1.1 2.5 29.0 19.2 2.2 36.7 13.0 4.6 39.2 2.5 30.8 106.1 4.7 4.6
5.6 1.9 4.4 30.1 19.7 2.1 37.3 14.4 3.9 40.9 2.5 32.4 107.8 4.8 4.9
7.5 3.0 7.0 30.7 19.9 2.0 37.6 15.1 3.7 41.9 2.5 33.2 108.7 4.8 5.1
90
3.8 1.1 2.5 27.3 18.5 2.5 35.8 11.0 5.6 42.2 2.6 33.5 109.1 4.8 5.2
5.6 1.9 4.3 28.4 19.0 2.3 36.4 12.2 4.9 44.1 2.6 35.2 110.9 4.9 5.6
7.5 2.9 6.8 29.0 19.2 2.2 36.7 12.9 4.6 45.1 2.7 36.0 111.8 5.0 5.8
100
3.8 1.0 2.3 25.6 17.7 2.8 35.0 9.2 6.7
Operation Not Recommended
5.6 1.8 4.1 26.7 18.2 2.6 35.5 10.3 6.0
7.5 2.8 6.5 27.2 18.4 2.5 35.8 10.9 5.6
110
3.8 0.9 2.2 23.8 16.9 3.1 34.4 7.7 8.0
5.6 1.7 3.9 24.9 17.4 2.9 34.8 8.6 7.2
7.5 2.7 6.2 25.5 17.6 2.8 35.0 9.1 6.8
120
3.8 0.9 2.0
5.6 1.6 3.7 23.1 16.5 3.2 34.2 7.1 8.5
7.5 2.6 6.0 23.7 16.8 3.1 34.4 7.6 8.1
†ARI/ASHRAE/ISO 13256-1 (WLHP applications) certi ed conditions are 86°F EWT, 80.6°F DB / 66.2°F WB
EAT in cooling and 68°F DB / 59°F WB EAT in heating.
Interpoaltion is permissable, extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling and 70°F DB in heating
All performance data is based upon the lower voltage of dual voltage rated units
See performance correction tables for operating conditions other than those listed above.
Operation below 60°F EWT requires optional insulated water circuit.
Operation below 40°F EWT is based upon 15% antifreeze solution.