Design Guide HEV-HEH SEriES Heat Controller
30
30
Engineering Design Guide HEV/H SERIES Heat Controller, LLC
Electrical Data
HE
Model
Volt
Code
Rated Voltage
Voltage
Min/Max
Compressor
HWG
Pump
FLA
Ext
Loop
Pump
FLA
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amp
Max
Fuse/
HACR
RLA LRA Qty
024 1 208-230/60/1 197/252 11.7 58.3 1 0.5 4.0 3.9 20.1 23.0 30
030 1 208-230/60/1 197/252 13.1 73.0 1 0.5 4.0 3.9 21.5 24.7 35
036 1 208-230/60/1 197/252 15.3 83.0 1 0.5 4.0 3.9 23.7 27.5 40
042 1 208-230/60/1 197/252 17.9 96.0 1 0.5 4.0 5.2 27.6 32.0 45
048 1 208-230/60/1 197/252 21.2 104.0 1 0.5 4.0 5.2 30.9 36.2 50
060 1 208-230/60/1 197/252 27.1 152.9 1 0.5 4.0 6.9 38.5 45.2 70
HACR circuit break in U.S. only Wire length based on one way measurement with 2% voltage drop
All fuses Class RK-5 Wire sizes based on 140°F (60°C) copper conductor