Heat Controller, Inc. HTV/HTD/HTH SERIES
48
Performance Troubleshooting
PERFORMANCE TROUBLESHOOTING
45
Performance
Troubleshooting
Htg Clg Possible Cause Solution
Check for dirty air filter and clean or replace
Check fan motor operation and airflow restriction
X Reduced or No Air Flow in Heating
Too high of external static. Check static valve
Check pump operation or valve operation/setting X Reduced or No Water Flow in Cooling
Check water flow adjust to proper flow rate
X Inlet Water too Hot Check load, loop sizing, loop backfill ground
X Air Temperature Out of Range in Heating Bring return air temp within design parameters
X Scaling in water heat exchanger Perform scaling check and clean if necessary
X X Unit Overcharged Check superheat and subcooling. Reweight in
charge
X X Non-condensables in System Vacuum system and reweigh in charge
High Head Pressure
X X Restricted Metering Device Check superheat and subcooling per chart
Check pump operation or water valve operation
Plugged strainer or filter. Clean or replace
X Reduced Water Flow in Heating
Check water flow adjust to proper flow rate
X Water Temperature Out of Range Bring water temp within design parameters
Check for dirty air filter and clean or replace
Check fan motor operation and airflow restrictions
X Reduced Air Flow in Cooling
Too high of external static. Check static valve
X Air Temperature Out of Range Too much cold vent air? Bring entering air temp to
design parameters
Low Suction Pressure
X X Insufficient Charge Check for refrigerant leaks
X Too High of Air Flow Check fan motor speed selection and airflow Low Discharge Air
Temperature in Heating
X Poor Performance See ‘Insufficient Capacity’
X Too High of Air Flow Check fan motor speed selection and airflow High Humidity
X Unit Oversized Recheck loads & sizing check sensible clg load
pump capacity