Heat Controller, Inc. HTV/HTD/HTH SERIES
4
General Information
All units have TXV devices, 1/2” and 3/4” electrical knockouts.
T
CAUTION!
DO NOT store or install
units in corrosive environments or in
locations subject to temperature or
humidity extremes (e.g., attics, rooftops,
etc.). Corrosive conditions and high
temperature or humidity can significantly
reduce performance, reliability, and service
life. Always move and store units in an
upright position. Tilting units on their
sides may cause equipment damage.
T
CAUTION!
CUT HAZARD
Failure to follow this caution may result in
personal injury. Sheet metal parts may
have sharp edges or burrs. Use care and
wear appropriate protective clothing, safety
glasses and gloves when handling parts
and servicing heat pumps.
CAUTION! CAUTION!
NOTICE! Failure to remove shipping brackets from spring-mounted compressors will
cause excessive noise, and could cause component failure due to added vibration.
Model 24 36 48 60
Compressor (1 Each)
Two-Stage Scroll
Factory Charge R410A (oz)
58 78 81 144
ECM Fan Motor & Blower
Fan Motor (hp)
½ ½ 1 1
Blower Wheel Size (dia x w) - (in)
9 x 7 11 x 10 11 x 10 11 x 10
Water Connection Size
Swivel (in)
1 1 1 1
HWG Connection Size
Swivel (in)
1 1 1 1
Coax Volume
Volume (US Gallons)
0.76 0.92 1.24 1.56
Vertical Upflow
Air Coil Dimensions (h x w) - (in)
28 x 20 28 x 25 32 x 25 36 x 25
Standard Filter - 1”
Throwaway, qty (in)
1 - 28 x 24 1 - 28 x 30 2 - 16 x 30 1 - 16 x 20
1 - 20 x 30
Weight - Operating, (lbs)
266 327 416 443
Weight - Packaged, (lbs)
276 337 426 453
All units have spring compressor mountings, TXV devices, and all units have ½” and ¾” electrical knockouts.
GeoMax2 TWO-STAGE HTV/HTD SERIES (60 Hz Only)
UNIT PHYSICAL DATA
70
156
1
11 x 10
1
1
36 x 25
443
453
1.56
1 - 16 x 20
1 - 20 x 30
UNIT PHYSICAL DATA
TWO STAGE HTV/HTD/HTH SERIES (60Hz Only)
Model 24 36 48 60 70
Compressor (1 Each) Two-Stage Scroll
Factory Charge R410A (oz) 58 78 81 144 156
ECM Fan Motor & Blower
Fan Motor (hp)
1
/2
1
/2 1 1 1
Blower Wheel Size (dia x w) - (in) 9 x 7 11 x 10 11 x 10 11 x 10 11 x 10
Water Connection Size
Swivel (in) 1 1 1 1 1
HWG Connection Size
Swivel (in) 1 1 1 1 1
Coax Volume
Volume (US Gallons) 0.76 0.92 1.24 1.56 1.56
Vertical Upow/Downow
Air Coil Dimensions (h x w) - (in) 28 x 20 28 x 25 32 x 25 36 x 25 36 x 25
Standard Filter - 2” Pleated
HERV11, Quantity - in x in
1-24 x 28 1-28 x 30 1-30 x 32 1-30 x 36
1-30 x 36
Weight - Operating, (lbs) 266 327 416 443 443
Weight -Packaged, (lbs) 276 337 426 453 453
Horizontal
Air Coil Dimensions (H x W), in 18 x 31 20 x 35 20 x 40 20 x 45 20 x 45
Standard Filter - 2” Pleated
MERV11, Quantity - in x in
2 - 18 x 18 1 - 12 x 20
1 - 20 x 25
1 - 18 x 20
1 - 20 x 24
2 - 20 x 24 2 - 20 x 24
Weight - Operating, lbs 266 327 416 443 443