Insulated Liquid Line
Tape
Sheet Metal Hanger
Correct Incorrect
Fig.5
Typical Installation
Fig.3 Tubing Hanger
Fig.4 Underground Installation
3.6 PRECAUTIONS DURING BRAZING OF LINES
Insulated Vapor Line
TO
INDOOR
BLOWER
TO
POWER
SUPPLY
TO
COIL
WEATHERPROOF
DISCONNECT
SWITCH
Seal opening(s) with
permagum or equivalent
24V control signal
NOTE:All outdoor wiring must be weather proof
All outdoor unit and evaporator coil connections are copper-to-copper and should be
brazed with a phosphorous-copper alloy material such as Silfos-5 or equivalent. DO
NOT use soft solder. The outdoor units have reusable service valves on both the liquid
and suction vapor connection. The total system refrigerant charge is retained within the
outdoor unit during shipping and installation. The reusable service valves are provided
to evacuate and charge per this instruction.
Serious service problems can be avoided by taking adequate precautions to assure an
internally clean and dry system.
11