17
NOTES: As only 2-digit numbers are available for the control display, the display will alter if
over 2 digits. For example 108 will display as A8,118 will display B8 and 128 will
display C8.
ERROR CODES
When an error occurs or the protection mode is set automatically, the wired controller will display an
error code as below.
Compressor exhaust gas temp. sensor
failure
Inlet water temp sensor failure
1) Sensor open circuit
2) Sensor short circuit
3) Main PCB damaged
1) Check the sensor connection
2) Replace the sensor
3) Replace the main PCB
Outlet water temp sensor failure
Protection for over-high inlet/outlet
water temp difference
1) Too low water flow
2) Main PCB damaged
1) Check the water filter and water
circuit (no blockages)
2) Replace the PCB
Ambient temp sensor failure
Protection for over-high inlet/outlet water
difference under cooling mode
1) Inadequate water flow rate
2) Inadequate inlet water temp
3) Main PCB damaged
1) Check the water filter and water
circuit (no block)
2) Adjust the setting temp to normal
working range
3) Replace the main PCB
Pump-off time after reaching setting
water temp.
Second anti-freezing mode
0(Heat pump)\
1(Electric heater)
0(cooling only)\1(cooling
and heating)\2(heating
only)