8 Control unit DC 6 – 01 ... 05
Digital Governor Basic System PANDAROS III 23
8 Control unit DC 6 – 01 ... 05
8.1 Specification
8.1.1 General
Supply voltage 12 V DC or 24 V DC
min. voltage 9 V DC
max. voltage 33 V DC
max. ripple voltage max. 10 % bei 100 Hz
Current consumption max. 7 A, and
max. 11 A for max. 60 Seconds
Permissible voltage dip at
maximum current consumption max. 10 % in control unit
Fuse protection of governor 12 A
Storing temperature -40°C up to +85°C
Operating temperature -40°C up to +80°C
Operating temperature LCD -10°C up to +60°C
optional -20°C up to +70°C
Humidity up to 98% at 55°C
Dynamic strength max. 2 mm at 10 up to 20 Hz,
max. 0,24 m/s at 21 up to 63 Hz
max. 7 g at 64 up to 2000 Hz
Shock 50 g, 11 ms- half-sine wave
Protection grade IP 00
Insulation resistance > 1 MOhm at 48 V DC
Weight approx. 0.5 kg
EMC Directives 2004/108/EC
2004/104/EG
according to EMC Standards: ISO 11452-2
ISO 7637-2 / -3
DIN EN 61000-6