16 | Assembly position
Long and narrow rooms
(e.g. hallways)
In rooms and hallways with a width
of < 1 m, the following assembly
position applies:
In a central position on the ceiling
between the walls
In hallways with a width of < 3 m, the
following assembly position applies:
Clearance to the front side:
max.7.5 m
Distance between 2 smoke alarms:
max. 15m
max 7.5m
max 7.5m
max . 3m
max . 3m
max. 15m
max 7.5m
max . 3m max . 3m
max. 15m max 7.5mmax 7.5m
max . 3m