Assembly position | 17
Wall assembly
The smoke alarm may be placed on
the wall of a room in the following
cases:
Ceiling-assembly is not possible
(e.g. in the case of textile ceilings
or ceiling heating)
Rooms and hallways with a
surface area of ≤ 6 m²
Kitchens which serve as escape
routes
The following conditions apply to
wall assembly:
In a central position on the longer
wall
Clearance to ceiling: 0.3 to 0.5 m
Clearance to objects below the
smoke alarm: 1 m
Lateral clearance: 0.5 m
In the event of other special
cases, e.g. rooms larger than
60 m² or ceiling joists, please
contact your dealer.
Smoke alarm wall installation
0.3 to 0.5 m
at least 1m
at least 0.5 m
i