19
Deutsch
|
Français
|
Nederlands
|
English
Installer menu exit
Press validation key
to exit user menu and return to the
main screen.
EEPROM clearing
All thermostat parameters will be loaded with factory settings.
Pressing and maintaining validation key
displays:
Anti-condensation function of the installation:
only with RH sensor
When condensation is detected, air conditioning is stopped or/
and dehumidifier is activated.
Default value: Yes Other value: no
Anti-short Cycle time ON
Setting time value of minimum ON-state load.
Time value is a number of minutes.
Default value: 2 minutes Other value: no to 5 minutes
Anti-short Cycle time OFF
Setting time value of minimum OFF-state load.
Time value is a number of minutes.
Default value: 2 minutes Other value: no to 5 minutes
Pump and valve exercises
Activation or not of system exercise function.
Default value: Yes Other value: no
Accessing to installer parameters
holding
button
holding
button
releasing
button
Clearing
is done