HID Aero™ X1100 Installation Guide
PLT-04233, Rev. A.36
Powering
Trusted Identities
LED POWER ON SELF-TEST NORMAL OPERATION
BATT FAIL On then OFF OFF = Inactive, ON = Active, Flash = Fault.*
AC FAIL On then OFF OFF = Inactive, ON = Active, Flash = Fault.*
TAMPER On then OFF OFF = Inactive, ON = Active, Flash = Fault.*
IN 1 On then OFF OFF = Inactive, ON = Active, Flash = Fault.*
IN 2 On then OFF OFF = Inactive, ON = Active, Flash = Fault.*
IN 3 On then OFF OFF = Inactive, ON = Active, Flash = Fault.*
IN 4 On then OFF OFF = Inactive, ON = Active, Flash = Fault.*
ONLINE ON for approximately 15 seconds
O-Line / On-Line and battery status.
On-Line = A long flash ON and a short flash OFF.
O-Line = A short flash ON and a long flash OFF.
Double flash if battery is low.
HOST COMM ON for approximately 1 second Host communication activity (Ethernet).
IO INTERNAL ON for approximately 1 second Internal IO module communication activity.
IO MODULE PORT 1 ON for approximately 1 second External IO module activity (Port 1).
IO MODULE PORT 2 ON for approximately 1 second External IO module activity (Port 2).
READER 1 ON for approximately 1 second
OSDP Mode = Flashes when transmitting data.
Wiegand or C&D Mode = Flashes when data is received,
either input.
READER 2 ON for approximately 1 second
OSDP Mode = Flashes when transmitting data.
Wiegand or C&D Mode = Flashes when data is received,
either input.
RELAY 1 OFF ON = Energized.
RELAY 2 OFF ON = Energized.
RELAY 3 OFF ON = Energized.
RELAY 4 OFF ON = Energized.
ETHERNET OFF
ETHERNET LED on Cover: Flashing = Ethernet activity
ETHERNET JACK:
Green/Left ON = good link
Yellow/Right is ON = 100 Mb/s and OFF = 10 Mb/s
*If this input is defined, every three seconds the LED is pulsed to its opposite state for 0.1 seconds, otherwise,
the LED is OFF.
Status LEDs