System Manual Compact Systems  4 Communication 
HI 800 141 E Rev. 2.02  Page 23 of 110 
Ethernet operation may be disturbed! 
Ensure that no network rings result from interconnecting the controllers. Data packets 
may only travel to a system over a single path. 
If controllers and remote I/Os with different versions of operating systems are connected via 
safeethernet, the following cases must be observed: 
Operating system of 
controller 
Operating system of 
remote I/O 
safeethernet connection possible? 
Table 15:  Connection of Controllers and Remote I/Os with Different Operating Systems 
Controllers with different operating system versions (CPU OS V7 and higher and CPU OS up to 
V7) can be connected with cross-project communication, refer to the communication manual (HI 
800 101 E) 
4.2.2  Maximum Communication Time Slice 
The maximum communication time slice is the time period in milliseconds (ms) and per cycle 
assigned to the processor system for processing the communication tasks. If not all upcoming 
communication tasks can be processed within one cycle, the whole communication data is 
transferred over multiple cycles (number of communication time slices > 1). 
When calculating the maximum response times allowed, the number of communication time 
slices must be equal to 1, see the communication manual (HI 801 101 E). The duration of the 
communication time slice must be set such that, when using the communication time slice, the 
cycle cannot exceed the watchdog time specified by the process. 
 
 
 
4.2.3  Connectors for safeethernet/Ethernet 
For networking via safeethernet/Ethernet, the compact systems are equipped with 2 or 4 
connectors, depending on the model, which are located on the housing's lower and upper sides. 
To interconnect the HIMatrix systems, only interference-free Ethernet cables may be used, e.g., 
shielded (STP)! 
4.2.4  Communication with the PADT 
A HIMatrix controller communicates with a PADT via Ethernet. A PADT is a computer that is 
installed with a programming tool, either SILworX or ELOP II Factory. The programming tool 
must comply with the operating system version of the controller. 
  CPU OS V7 and higher: SILworX 
  CPU OS up to V7: ELOP II Factory 
The computer must be able to reach the controller via Ethernet. 
A controller can simultaneously communicate with up to 5 PADTs. If this is the case, only one 
programming tool can access the controller with write permission. The remaining programming 
tools can only read information. If they try to establish a writing connection, the controller only 
allows them a read-only access.