System Manual Compact Systems  7 Start-Up 
HI 800 141 E Rev. 2.02  Page 85 of 110 
External devices that should communicate with HIMatrix controllers must have the following 
network settings: 
Table 56:  Permissible Communication Settings for External Devices - CPU OS up to V7 
The following network settings are not allowed: 
Table 57:  Impermissible Communication Settings for External Devices - CPU OS up to V7 
COM OS V8.32 and Higher and ELOP II Hardware Management V7.56.10 and Higher: 
The operating parameters of each Ethernet port on the integrated Ethernet switch can be set 
individually. 
For HIMatrix controllers and remote I/Os with extended settings, set the Speed Mode and Flow 
Control Mode to Autoneg. To ensure that the parameters of this dialog box become effective, 
the option Activate Extended Settings must be selected, see Figure 11. 
Figure 11:  Communication System Properties - CPU OS up to V7 
The parameters ARP, MAC Learning, IP Forwarding, Speed Mode and Flow Control Mode are 
explained in details in the ELOP II Factory online help. 
Replacement of one controller with identical IP address: 
If a controller has its ARP Aging Time set to 5 minutes and its MAC Learning set to 
Conservative, its communication partner does not adopt the new MAC address until a period 
of 5 to 10 minutes after the controller is replaced. During this time period, no communication is 
possible with the replaced controller. 
The port settings of the integrated Ethernet switch on a HIMatrix resource can be configured 
individually starting with the following versions. 
  V8.32 of the communication operating system and 
  V7.56.10 of ELOP II Hardware Management 
Select Ethernet Switch -> New -> Port Configuration to define the configuration parameters 
for each switch port.