System Manual Compact Systems  7 Start-Up 
HI 800 141 E Rev. 2.02  Page 75 of 110 
LL Alarm 
Acknowledgment 
Required 
The user must confirm that the lowest limit (LL) has 
been exceeded (acknowledgment). 
The user may not confirm that the lowest limit (LL) 
has been exceeded. 
Default value: Deactivated 
Checkbox activated, 
deactivated 
The hysteresis avoids that many events are continuously created 
when the process value often oscillate around a limit. 
Depending on the 
global variable type 
Table 45:  Parameters for Scalar Events 
Faulty event recording due to improper parameter settings possible! 
Setting the parameters L Alarm Value and H Alarm Value to the same value can cause an 
unexpected behavior of the event recording since no normal range exists in such a case. 
For this reason, make sure that L Alarm Value and H Alarm Value are set to different 
values. 
 
 
7.7  Configuring a Resource Using ELOP II Factory - CPU OS up to V7 
This chapter describes the various configuration options using ELOP II Factory for processor 
operating systems up to V7. 
7.7.1  Configuring the Resource 
The first step is to configure the resource. The parameter and switch settings associated with 
the configuration are stored to the NVRAM of the processor system and to the flash memory of 
the communication system. 
The following system parameters can be set for a resource: 
System ID within the network 
Safety time of the controller 
(not of the entire process) 
 10 ms 
 (Safety 
Time) / 2 
 5000 ms 
Maximum time allowed for a PES RUN 
cycle. 
If the cycle time has been exceeded, the 
controller enters the STOP state. 
Controller: 
50 ms 
Remote I/O: 
10 ms 
The main enable switch can only be set to 
ON if the controller is in the STOP state. 
It allows the user to modify the settings for 
the following switches and the parameters 
Safety Time and Watchdog Time in the RUN 
state. 
Automatic start of the controller after its 
powering ON (automatic transition from 
STOP to RUN) 
Start command for the controller 
Start (cold start) or restart (warm start) 
commands accepted by the controller 
Start/restart not allowed