3 Product Description X-DO 32 01
Page 26 of 52 HI 801 097 E Rev. 4.00
3.7 System Cable X-CA 006
The X-CA 006 system cable is used to wire the X-CB 009 03/04 connector board with the
field zone via field termination assemblies.
General
Cable LIYY 64 x 0.34 mm² +
2 x 2 x 0.25 mm²
Wire Finely stranded
Average outer diameter (d) approx. 17.2 mm
Minimum bending radius
Fixed laying
Flexible application
5 x d
10 x d
Combustion behavior
Flame resistant and self-extinguishing in
accordance with IEC 60332-1-2, -2-2
Length 8…30 m
Color coding Based on DIN 47100, see Table 13.
Table 14: Cable Data
Identical Cable Plugs
Figure 8: System Cable X-CA 006 01 n
The system cable is available in the following standard variants:
System cable Description Length
X-CA 006 01 8 8 m
X-CA 006 01 15 15 m
X-CA 006 01 30
Coded cable plugs on both sides
30 m
Table 15: Available System Cables

Table of Contents