4 Start-up X-DO 32 01
Page 38 of 52 HI 801 097 E Rev. 4.00
4.4.4 Submodule Status [DWORD]
Coding of the variable Submodule Status.
Coding Description
0x00000001 Fault in hardware unit (submodule).
0x00000002 Reset of an I/O bus
0x00000004 Fault detected while configuring the hardware
0x00000008 Fault detected while verifying the coefficients
0x00000010 First temperature threshold exceeded (warning temperature)
0x00000020 Second temperature threshold exceeded (limit temperature)
0x00000040 Overcurrent, module shutdown
0x00000080 Reset of CS monitoring (Chip Select monitoring)
0x00000100 Hardware fault in short-circuit monitoring
0x00800000 Voltage monitoring of WD1: voltage error
0x01000000 Voltage monitoring of WD2: voltage error
0x02000000 Voltage monitoring of L1+ HIGH voltage defective
0x04000000 Voltage monitoring of L1+ LOW voltage defective
0x08000000 Voltage monitoring of L2+ HIGH voltage defective
0x10000000 Voltage monitoring of L2+ LOW voltage defective
0x20000000 Voltage monitoring of AGND voltage defective
0x40000000 Voltage monitoring of VMOS HIGH voltage defective
0x80000000 Voltage monitoring of VMOS LOW voltage defective
Table 20: Submodule Status [DWORD]