MAINTENANCE | PAGE 29
NOTE
The existence of modules with the same ID is not permitted. If during start up a
display module detects another analogue module with the same ID, the
message will be displayed ERROR ID. DISPLAY.
NOTE
By changing the ID of a module, it automatically restarts. It is important to NOT
change the ID of measurements modules with the genset in operation.
8.2.2. ALLOCATION OF IDS
Because all the electronic modules have the ID 0 by default, for the
implementation of installations with multiple control units interconnected, it is
necessary to assign IDs to the various modules. For this purpose, it is necessary
to progressively switch on the various control units, assigning each of them
different IDs as they are connected.
8.3 RESETTING THE CURRENT MEASUREMENTS
In the event of an incorrect current reading when the genset is uncharged, it is
possible to perform a zero calibration (Measurements table, parameters 6, 8 and
10: any of the 3 perform the resetting of the 3 current channels) of the
Measurements table.