The control unit must be mounted at the front of an electrical panel, if possible in
the centre to allow easy wiring. There are no special ventilation requirements due
to the low power that the control unit consumes.
All outputs must be provided with the corresponding inductive current disconnec-
tion devices (diodes, varistors, RC lters, etc…).
The wiring for manoeuvres should be kept at a sufcient distance from high elec-
tric elds: at least two metres of power lines of up to 600A and 1 metre of power
lines over 600A.
5.2 ELECTRICAL CHARACTERISTICS
Symbol Parameter Conditions
Mini-
mum
Typical
Maxi-
mum
Unit
Power supply (terminals 8÷36V, –BAT, +BAT)
8÷36 V Module supply voltage 8 36 VDC
+BAT Power supply of the outputs 8 36 VDC
I
BAT
Supply current 8÷36 V=12 V 20 60 mA
I
BAT
Supply current 8÷36 V=24 V 10 50 mA
P
BAT
Power consumption 1 W
NPN digital inputs (terminals RC, BPA, ATA, LT, PEM, AUX)
V
IN
Input voltage -0.7 40 V
V
IL
Low level input voltage 1 V
V
IH
High level input voltage 5 V
I
IL
Low level input current V
IN
= 0V 2 2.5 mA
I
IH
High level input current V
IN
= 24V 0 100
uA
Pick-Up / Generator input sensor (terminals GCOM, PCK, GEN)
V
IN
Pick-Up input voltage 4 30 VDC
F
IN
Pick-Up input frequency 200 2500 8000 Hz
V
IN
Generator input voltage 180 480 VAC
F
IN
Generator input frequency 45 66 Hz
Power PNP outputs (terminals ARR, PR, PC)
V
O
Output voltage +BAT V
I
O
Output current T = 1s 40 A
I
O
Output current T = 10s 20 A
I
O
Output current T = ∞ 15 A
PNP outputs (terminals D+, AL, PD, CON)
V
O
Output voltage +BAT V
I
O
Output current 1 A
R
D+
Output resistance D+ 49.5 Ω
Environmental conditions and protection of the enclosure
T
o
Operating temperature -40 +85 ºC
H
R
Relative humidity
No conden-
sation
80 %
IP Degree of Protection *see note 1 65
Note 1: IP 65 on the front of the control unit when installed on the control panel with the sealing gasket
provided.
5.3 DIMENSIONS OF THE EQUIPMENT
66 76.5
83.5
66
66
78
78
5.4 CHARACTERISTICS AND INSTALLATION OF THE EQUIPMENT
The equipment is included within the measurement category CAT III 600V for
measurements performed in the building installation. Disconnection means
should be incorporated to the xed installation in accordance with installation
regulations. Such means must have contact separation for all poles that provide
full disconnection in category III overvoltage conditions.
The disconnecting means must be accessible by the user. The negative terminal
of the battery, the chassis of the electrical panel and the chassis of the genera-
tor set must all be earthed.
This equipment can generate the risk of danger if handled improper-
ly. It must be installed by qualied personnel. It is necessary to
consult the equipment 's documentation.