10
Installation EAGLE One
Release
03
07/2014
CONTROL DRAWING to EAGLEONE and TOFINOXE series
for Use in Hazardous Locations
Class I Division 2, Groups A, B, C, D
Rev. 0 Document No.: 000174247DNR Page 1/2
MSP30 / MSP32
Groups A, B, C, D
Hazardous Location
Ordinary Location, Non-Hazardous Area,
1 2 3 4
4 3 2 1
The earth conductor must be
at least of the same wire size
(mm² or AWG) as the supply
conductors.
Nonincendive field wiring parameters:
THE RELAY TERMINALS ARE DEPENDENT
UPON THE FOLLOWING
ENTITY PARAMETERS: *)
Nonincendive field wiring parameters:
THE USB POWER SUPPLY CONTACTS ARE
DEPENDENT UPON THE FOLLOWING
ENTITY PARAMETERS: *)
5,5 V 1.25A 10 µF 10 µH
FAULT contacts
USB pin 4
USB pin 1
Any
EAGLEONE-0200xxx or
TOFINOXE-0200xxx device