Installation EAGLE One
Release
03
07/2014
For Use in explosive atmospheres according to the European directive 94/9/EC:
Applied Standards: EN60079-0, 2012
EN60079-11, 2012
EN60079-15, 2010
The Use in Hazardous Locations with explosive atmospheres is only allowed for EAGLEONE or TOFINOXE model
No´s. which are labeled accordingly – including “
8
II 3G” , “Ex nA IIC ic T4 Gc” , “DEKRA 13ATEX0184X”
SPECIAL CONDITIONS FOR SAFE USE:
The modules shall be installed in a suitable enclosure providing a degree of protection of at least IP54 according
to EN60529, taking into account the environmental conditions under which the equipment will be used.
Provisions shall be made to prevent the rated voltage from being exceeded by transient disturbances of more
than 119V.
When the temperature under rated conditions exceeds 70°C at the cable or conduit entry point, or 80°C at the
branching point of the conductors, the temperature specification of the selected cable shall be in compliance with
the actual measured temperature values.
Manufactured in 72654 Neckartenzlingen / Germany by Hirschmann Automation and Control GmbH.
DOM: ww/yyyy (Date of manufactur w - week, Y - year. Refer to the device label).
CONTROL DRAWING to EAGLEONE and TOFINOXE series
according to the European Directive 94/9/EC
Rev. 0 Document No.: 000174247DNR Page 2/2