Troubleshooting
© 2008 HIRSCHMANN Automation and Control GmbH · Branch Office Ettlingen · eMail: info.ecs@hirschmann.de · www.hirschmann-usa.com 46
50 650 19 0201e_Rev C (LinkBelt278).doc / 2008-08-18 / Rev. C / rk
7.2 LMI System Malfunction Table (LMLG V 1.x)
Fault
code
Error Cause Elimination
E01
Lowered below radius
range or angle range
exceeded
Fallen below the minimum
radius or gone past the maxi-
mum angle specified in the re-
spective load chart due to rais-
ing the boom too far
Lower the boom to a ra-
dius or angle specified in
the load chart.
E02
Radius range ex-
ceeded or lowered
below angle range
Gone past the maximum radius
or lowered below the minimum
angle specified in the respec-
tive load chart due to lowering
the boom too far
Raise the boom to a radius
or angle specified in the
load chart.
A non existing operating mode
has been selected
Set the correct operating
mode for the operating state
in question
The boom is in a non-permitted
slewing zone
Slew the boom to a permit-
ted area.
E04
Operating mode not
acknowledged or non
permitted slewing zone
The selected operating mode is
not available in the Flash-
EPROM or blocked
Check the Data software in
the Flash-EPROM
A non existing main boom
length has been selected
Set the correct main boom
length for the operating
state in question
E05
Main boom length not
available
The selected main boom length
is not available in the Flash-
EPROM or blocked
Check the Data software in
the Flash-EPROM
E06
Radius range ex-
ceeded or lowered
below angle range with
luffing jib operation
Maximum radius as specified in
the load chart exceeded or low-
ered below minimum angle due
to lowering the luffing jib too far
Raise the jib to a radius or
angle specified in the load
chart.
E07
Overload relays check
Relays = overload active and
CU input 20 = on
Relays = no overload and CU
input 20 = off
Check cable to overload
relays and CU input 20
Check relays
Check CU input 20
Cable between the central unit
and the force transducer defec-
tive or loose. Water inside the
plug of the transducer
Force transducer defective
Check cable as well as
plugs, replace, if need be
Replace force transducer
E14
Below lower limit value
in measuring channel
"force main boom right"
Electronic component in the
measuring channel is defective.
Replace sensor unit
Cable between the central unit
and the angle sensor defective
or loose. Water inside the plug
of the angle sensor
Angle potentiometer defective
Check cable as well as
plugs, replace, if need be.
Replace angle sensor
E15
Below lower limit value
in measuring channel
"angle main boom"
Electronic component in the
measuring channel defective.
Replace sensor unit
E16
Below lower limit value
in measuring channel
"angle luffing jib"
Refer to E15
Refer to E15
E17
Below lower limit value
in measuring channel
"force luffing jib left"
Refer to E14 Refer to E14